Air Density and Specific Volume @ Air Inlet must be
based on the dry bulb temperature at a relative humidity,
not on wet bulb temperature. Let's find a dry bulb temperature
from Psychrometric chart or from the following computer
calculation method.

The dry bulb temperature
corresponding 80% RH at 80oF WBT is 85.24oF.
(Note: Some engineers are using the air density and
specific volume at the air inlet using the web bulb
temperature. This is totally wrong and is quite different
from the value at the dry bulb temperature & relative
humidity.)
Specific Volume @ 85.24 DBT
& 80% RH = 14.2230 ft3/lb
Airflow Volume @ Air Inlet = Air Mass Flow x Specific
Volume @Air Inlet= 68,271.5 x 14.2230= 971,028 ft3/min
(For reference, the specific volume at the given wet
bulb temperature is 14.1126 ft3/lb and airflow
volume becomes 963,485 ft3/min. Compare this
value with above airflow volume.)
Air Velocity @ Air Inlet
= Airflow Volume @ Air Inlet / Net Area of Air Inlet=
971,028 / 1,134 = 856.29 ft/min (FPM)
Air Density @ 85.24 DBT & 80% RH = 0.0718 lb/ft3
Pressure Drop Coefficient for this arrangement = 2.5
Then, pressure drop is obtained
from below:
Pressure Drop = K (V / 4008.7)2
x Density Ratio= 2.5 x (856.29 / 4008.7)2
x (0.0718 / 0.0750)= 0.1092 inch Aq.
(For reference, the air density at the given wet bulb
temperature is 0.0724 lb/ft^3. Compare this with the
previous value of air density.)
Download the example file
(exe6_1.zip)
Example 6-2. Determine
the pressure drop at the fill for the same example 6-1.
(Solution)
First, it is to calculate the average air velocity through
the fill. The reasons why the average air velocity must
be calculated are based the assumptions below;
1) The heat exchange in the
rain zone is negligible and there is no change in the
air between the entering air into the tower inlet and
into the bottom of fill.
2) The heat is completely exchanged at the fill section
& water distribution zone.
3) The exit air from the fill is 100% saturated and
the heat of exit air transferred from the water is considered
as an adiabatic process.
To calculate the average
air velocity, the average air volume and specific volume
through the fill must be calculated.
Average Specific Volume =
2 / (1 / Specific Volume @ Tower Inlet Temp. + 1 / Specific
Volume @ Tower Exit Air Temp.)
Specific Volume @ 85.24 DBT
& 80% RH = 14.2230 ft3/lb
Specific Volume @ 97.0 DBT & 100% RH = 14.9362 ft3/lb
(The exit temp. was guessed.)
Therefore, the average specific
volume at the fill = 14.5709 ft3/lb
Then, the average air volume at the fill is obtained
from Average Specific Volume x Air Mass Flow. That is,
the average air volume at the fill = 994,776.8 ft3/min
Average Air Velocity = Average Air Volume / Net Fill
Area
Net Fill Area = (Cell Length x Cell Width) x (1 - %
Fill Obstruction / 100)
% Fill Obstruction = (Sectional Area of Column x Number
of Columns) / (Cell Length x Cell Width) x Margin x
100(%)= (4 x 4 / 144 x 7 x 7) / (42 x 42) x 3.6 x 100
(Note: Safety margin for wood tower is about 3.6)= 1.11%
Therefore, the net fill area = (42 x 42) x (1 - 1.11
/ 100) = 1,730.7 ft2
Average Air Velocity @Fill = Average Air Volume @Fill
/ Net Fill Area= 574.78 ft/min
Second, the water loading
calculation is required as follows;
Water Loading = Tower Water
Flow Rate / Net Fill Area
= Design Water Flow Rate x (1 - % By-Pass Water / 100)
/ Net Fill Area = 12,500 x (1 - 3.27 / 100) / 1,730.7
= 6.99 GPM/ft2
Air Density @ 85.24 DBT &
80% RH = 0.0718lb/ft3
Air Density @ 97.0 DBT & 100% RH = 0.0696 lb/ft3
Then, average air density at fill = 0.0707 lb/ft3
Now, all the parameters are
ready to compute the pressure drop at the fill. The
calculation of pressure drop at the fill is very complicated
and it is impossible to predict the pressure drop if
the formula for the pressure drop is not available.
The formula of calculating the pressure drop at the
fill is a proprietary data of fill maker.
Pressure Drop @Fill = 0.3011
inch WG.
Example 6-3. Determine
the pressure drop at the drift eliminator per the given
conditions in example 6-1.
(Solution)
In general, the obstruction area in the drift eliminator
is considered same as the fill obstruction area. Therefore,
the net drift eliminator area = (42 x 42) x (1 - 1.11
/ 100) = 1,730.7 ft2. There is no change
in the air mass flow through out the cooling tower.
Therefore, the value of air mass flow is same as the
above obtained value of 68,271.47 lb/min. The air density
and specific volume at 97oF 100% RH are 0.0696
lb/ft3, 14.9362 ft3/lb respectively.
Then, the air volume at
the drift eliminator is obtained from Specific Volume
x Air Mass Flow.
That is, the air volume at the drift eliminator = 1,019,716.3
ft3/min
Air Velocity @ Drift Eliminator = Airflow Volume @ Drift
Eliminator / Net Area of Drift Eliminator
Air Velocity @ Drift Eliminator = 589.19 ft/min
Pressure Drop Coefficient for a general module type
of drift eliminator = 1.6 to 2.0
Then, pressure drop is obtained
from below:
Pressure Drop = K (V / 4008.7)2
x Density Ratio= 1.8 x (589.19 / 4008.7)2
x (0.0696 / 0.0750)= 0.0361 inch Aq.
Example 6-4. Determine
the pressure drop at the fan inlet of fan stack per
the given conditions in example 6-1. Let's assume that
the 28 feet of fan in the diameter with the 88 inch
of air seal disk was used and the fan inlet shape is
rounded. (R/D = 0.10)
(Solution)
The pressure drop is occurring at the fan inlet of fan
stack unless the shape of fan inlet is elliptical bell
and no obstruction under the fan in case of induced
draft fan arrangement. The following table could be
applied to the cooling tower fan stack as a guide line
in choosing the pressure drop coefficient.
Inlet
Shape
|
K
|
Extra
Factor
|
Total
Factor
|
Elliptical
(L/D = 1:1.5)
|
0.00
|
0.10
|
0.10
|
R/D
= 0.15
|
0.00
|
0.10
|
0.10
|
R/D
= 0.10
|
0.04
|
0.14
|
0.18
|
R/D
= 0.05
|
0.13
|
0.15
|
0.28
|
R
= 0
|
0.40
|
0.20
|
0.60
|
In practice, it is quite
essential to add some extra to the above K value since
there are a lot of obstructions under the fan. It is
considered that there is no change in the heat from
the drift eliminator to the fan. Accordingly, the specific
volume at the fan is same as the value at the drift
eliminator. Let's calculate the net fan area.
Fan Net Area = 3.1416 / 4
x (Fan Dia2 -Air Seal Disk2)=
573.52 ft2
Air Velocity @ Fan = Airflow Volume @ Fan / Net Fan
Area= 1019716.3 / 573.52 = 1778.00
Air Velocity @ Fan = 1,778.00 ft/min
(Note: The air volume at
fan is same as the air volume at the drift eliminator.)
Then, pressure drop is obtained
from below:
Pressure Drop = K (V / 4008.7)2 x Density
Ratio= 0.18 x (1778.0 / 4008.7)2 x (0.0696
/ 0.0750)= 0.0329 inch Aq.
|